Chapters:
15.04 Building Code
15.08 Standards for New Construction, Alterations and
Repairs
15.12 Building Operations
15.16 Dangerous Buildings
15.20 Moving Buildings
15.24 Fire Limits
15.28 Fire Prevention Code
15.36 Swimming Pools
15.40 Property Maintenance Code
15.44 Fair Housing Regulations
15.101 Administration, Enforcement, Fees and Penalties
(Footnotes)
BOCA
|
Sections:
15.28.010
Fire Prevention Code, Life Safety Code - adopted - modifications.
The provisions
of a) the ICC International Fire Prevention Code, 2003 edition as published
by the International Code Council, Inc. 4051 West Flossmoor Road, Country
Club Hills, IL 60478-5795, and b) the NFPA 101 Life Safety Code, 2003
edition, published by the National Fire Protection Association, 1 Batterymarch
Park, Quincy, Massachusetts 02169-7471, are hereby adopted by reference
as if fully set forth herein, together with the amendments listed herein,
for the purpose of prescribing regulations governing conditions hazardous
to life and property from fire or explosion. These codes and amendments
thereto shall be known as the “City of St. Charles Fire Prevention
Code.”
(Ord. 2004-M-76
§ 1; Ord. 1988-M-15 § 1; Ord. 1978-M-37 Art. 1.)
15.28.020
Bureau of Fire Prevention – Establishment & Duties.
- The
Fire Prevention Code shall be enforced by the Bureau of Fire Prevention
in the department of the City, which is established and which shall
operate under the supervision of the Chief of the Fire Department.
-
The person in charge of the Bureau of Fire Prevention shall be designated
by and serve at the pleasure of the Chief of the St. Charles Fire Department.
-
The Chief of the Fire Department may detail such members of the Fire
Department as inspectors as shall from time to time be necessary.
-
Reports of the Bureau of Fire Prevention shall be made periodically
and transmitted to the chief executive officer of the municipality;
said reports shall contain all procedures under this Code, with such
statistics as the Chief of the Fire Department may wish to include therein.
The Chief of the Fire Department shall also recommend any amendments
to the Code, which, in his judgment, shall be desirable.
(Ord. 2004-M-76
§ 1; Ord. 1978-M-37 Art. 2.)
15.28.030
Definitions.
- Wherever
the words “Fire Prevention Code” or “Code” are
used, they shall be held to mean the City of St. Charles, Illinois,
Fire Prevention Code.
-
Wherever the word “Municipality” is used in the Fire Prevention
Code, it shall be held to mean the City of St. Charles, Illinois.
-
Wherever the term “Corporation Counsel” is used in the Fire
Prevention Code, it shall be held to mean the City Attorney for the
City of St. Charles, Illinois.
-
Wherever the term “Fire Officials,” “Fire Inspector,”
“Inspector,” “Code Official,” “Authority
Having Jurisdiction,” or “Fire Marshal” is used, it
shall be held to mean the Fire Marshal of the City of St. Charles, Illinois.
-
Wherever the term “Bureau of Fire Prevention” is used, it
shall be held to mean the Bureau of Fire Prevention of the City of St.
Charles, Illinois.
(Ord. 2004-M-76
§ 1; Ord. 1988-M-15 § 1; Ord. 1978-M-37 Art. 3.)
15.28.040
Limits for the storage, handling, processing, manufacturing and transportation
of flammable, hazardous or toxic chemicals, liquids and gases.
-
Prohibited Storage of Explosives and Blasting Agents. The storage, handling
and use of explosives and blasting agents are hereby prohibited.
-
Prohibited Storage of Flammable and Combustible Liquids. The storage
of flammable and combustible liquids in outside, above-ground tanks
is hereby restricted as follows: As approved by the Fire Prevention
Code by the City of St. Charles, Illinois 60174. See F-2206.2.3.
-
Prohibited Storage and Manufacturing of Fireworks. The manufacture,
sale, handling, use or storage of fireworks is prohibited within the
corporate limit of the City of St. Charles. See F-3301 (pg. 265), Explosives
& Fireworks.
-
Restricted Bulk Storage of Liquefied Petroleum Gases. The bulk storage
of liquefied petroleum gases in excess of 500 gallons of water capacity
is hereby prohibited.
-
Motor Vehicle Routes for Transporting Hazardous Chemicals and Other
Dangerous Articles Including Liquefied Petroleum Gases and Combustible
and Flammable Liquids. Routes for vehicles transporting hazardous chemicals
and other dangerous articles including combustible and flammable liquids
are hereby established as follows:
1. Routes approved by the state or federal governments.
2. No tank vehicles shall be parked for over one hour or left unattended
at any time.
(Ord. 2004-M-76
§ 1; Ord. 1988-M-15 § 1; Ord. 1978-M-37 Art. 4.)
15.28.050
Amendments to the ICC International Fire Prevention Code 2003.
1. Section
101.1 insert the name of jurisdiction: “City of St. Charles, Kane
and DuPage Counties, Illinois.”
2. Section
105.6.28, including exceptions 1 and 2, is hereby deleted in its entirety
and the following shall be substituted therefore:
105.6.28
LP-gas. An operational permit is required for any storage and
use of LP-gas over 30 gallons water capacity.
3. Amend
Section 108.3 to read as follows:
108.3
Qualifications. The City Council of the City of St. Charles,
Illinois, shall serve as the Board of Appeals.
4. Amend
Section 307.1 (pg. 26) to read as follows:
307.1
General. A person shall not cause or allow open burning except
as provided by City Ordinance or by Special Permit.
5. Amend
Section 307.2 (pg. 26) to read as follows:
307.2
Permit Required. Open burning other than allowed by City Ordinance
shall be allowed only after applying for and receiving a special permit
from the Bureau of Fire Prevention for controlled burning for range
and wildlife management practices, prevention or control of disease
or pests, or special functions.
Open burning
shall only be allowed when the following requirements have been met:
- A
special permit shall be requested by and issued to the owner of the
property upon which the burning is to be kindled.
-
Applications for open burning shall be submitted in writing at least
fifteen (15) days before the fire is to be kindled.
-
All applications shall, as a minimum, contain information regarding
the purpose of the burning, the nature, and approximate quantities
of material to be burned, the date, time, and location of the burning
site.
-
The location of the burning site shall be not less than fifty (50)
feet from any structure.
-
No flammable or combustible liquids or solids shall be used to start
or assist in starting or assist in the accelerated spread of the fire.
-
The fire shall not be used for waste disposal purposes and the fuel
shall be chosen to minimize the generation of air contaminates.
-
Only clean, well-seasoned wood shall be used. Wood which has been
coated on the surface or pressure treated with any chmical that is
in any way harmful or hazardous to a person’s health or well-being
shall not be used.
-
The fire shall not burn for more than two (2) hours.
-
Any open burning shall be constantly attended until the fire has been
extinguished.
-
Fire estinguishment equipment shall be available for immediate use.
-
All open burning shall be prohibited when atmospheric conditions or
local circumstances make such fires hazardous.
-
Open burning prohibited: The Fire Official shall order the extinguishment,
by the permit holder, or the Fire Department, of any open burning
which creates or adds to a hazardous condition or objectionable situation.
6. Section
307.3.1 (pg. 27) Bonfires is hereby deleted in its entirety.
7. Amend
Section 307.3.2 (pg. 27) Recreational Fires to include outdoor fireplaces
or pits.
8. Section
308 (pg. 27) Open Flames is hereby amended as follows:
a) 308.3.2
Open flame decorative devices. Delete exception #10.
b) 308.3.5 Religious ceremonies. Delete in its entirety.
c) 308.3.7 Group A occupancies. Delete exceptions #1, 2, & 3.
9. Section
311.2.2 (pg. 29) Fire Protection. Delete Exceptions #1 and 2.
10. Add
Sections 315.4, 315.5 and 315.6 as follows:
315.4
Stock Maintenance. All stock shall be kept in a neat, orderly,
compact manner in accord with good housekeeping practices. Storage shall
not be within two (2) feet of the ceiling or the floor or roof structural
members, eighteen (18) inches from the sprinkler heads nor shall storage
obstruct egress from a building.
315.5
Packing Materials. Wherever and whenever stock is dispensed
directly from a shipping container and combustible material is used
as protective packing, such packing material shall be removed from the
container and taken care of by removing to the outside in closed containers.
Such containers shall be kept closed at all times except when removing
stock therefrom.
315.6
Removal of Packing and Waste Materials. No persons shall store
in any building excess amounts of combustible empty packing cases, wooden
or plastic pallets, barrels, boxes, rubber tires, shavings, excelsior,
rubbish, paper bags, litter, hay, straw and similar combustibles. Aisleways
and storage of the above mentioned combustibles necessary for the performance
of business shall be kept in an orderly and neat manner. Combustible
materials shall be removed daily or more often as is necessary to suitable
vaults, bins, dumpsters, compactors or separate buildings. Such practices
shall be as approved by the Fire Marshal.
11. Add
Section 316 as follows:
316
Miscellaneous Provisions
316.1
Tenant Separation. Each tenant space shall be separated from
other tenant spaces and corridors by walls, partitions, and floor-ceiling
assemblies having at least a one- (1-) hour approved fire resistance
rating.
316.2
Hazardous Areas. Rooms used for storage, boiler or furnace
rooms, fuel storage, janitors closets, maintenance shops, electric utility
rooms, kitchens, sprinkler rooms and similar uses shall be separated
from other building areas by assemblies having a fire resistance rating
of not less than one hour with appropriate protection of openings into
the rooms.
316.3
Fire Procedure Notice. Owners, managers, and agents of multiple
dwelling units with three (3) or more units, motels, hotels and places
of assembly shall post and maintain in a conspicuous location within
each dwelling unit and in access routes, a written notice which explains
what procedures to use in the event of a fire. The notice shall contain
a diagram of all fire exits.
316.4
Fire Extinguishers. Each building, other than single family
residential, shall be equipped with one or more fire extinguishers of
a type, size, and location as specified by the Fire Marshal.
12. Add Sections 503.7, 503.7.1, 503.7.2, 503.7.3, 503.7.4, 503.7.5, 503.7.6,
503.7.7, 503.7.8, 503.7.9, 503.7.10 and 503.7.11 as follows:
503.7
Public Access and Fire Lanes on Private Property, Devoted to Public
Use, shall be provided so that:
503.7.1
Public or private access is provided to each building so that the first
responding fire department pumper unit will be able to be so located
that all points of the interior of the building may be reached by one
hundred fifty (150) feet of initial attack hose.
503.7.2
Where the size or height of the building does not allow this regulation
to be met, an interior standpipe system equipped with fire departmet
hose connections approved by the Fire Official may be allowed as an
exception. The standpipe system shall be connected to a public water
system.
503.7.3
Design and installation shall meet the design criteria for
a Class I or III system of NFPA No. 14.
503.7.4
Public or private access for motor fire apparatus shall be provided
around the building so that there may be proper operation of ladders
and mechanically elevated mechanisms. Minimum width of the fire lanes
shall be 20 feet with greater widths to accommodate vehicles when turning
and laddering buildings.
503.7.5
Access routes shall be so arranged that fire department apparatus may
respond from all points of the building to adjacent fire hydrants along
routes not to exceed three hundred (300) feet from the most remote point
to the building to the closest fire hydrant.
503.7.6
Fire lanes on private property shall be approved by the Fire Marshal,
and parking of motor vehicles otherwise obstructing such fire lanes
or access routes shall be prohibited at all times. Permanent all-weather
signs identifying fire lanes and access ways shall be posted.
503.7.7
Public or private fire department access roads and ways shall be all
weather, properly maintained and accessible at all times. Such access
roads and ways shall be a minimum of six (6) inches of granular stone
surfaced by at least two (2) inches of bituminous asphalt material or
such other construction acceptable to the Fire Marshal.
503.7.8
Access roads shall be not less than fifteen (15) feet from the building
and further if the height of the building requires a greater setback
to ladder the buildings.
503.7.9
Access routes shall be continuous around the building.
503.7.10
This requirement may be modified by the Fire Marshal where adequate
building access openings and a complete fire suppression system are
provided.
503.7.11
Where cul de sacs are permitted, they shall not be less than ninety
(90) feet in diameter. The maximum length of the cul de sac shall be
one hundred (100) feet.
13. Add Sections 506.3, 506.4, 506.5 and 506.6, as follows:
506.3
Purpose and applicability. The purpose of the rapid entry key
system is to allow the fire department to gain immediate access to a
building in emergency situations without forcible entry. The Fire Marshal
shall require all buildings to have an approved key box system. An application
form is available at the Fire Prevention Bureau Office.
506.4
Location. The installation of the approved key box shall be
approved by the Fire Marshal. The box shall be located not more than
six (6’) feet above grade. The key box may be supervised by a
tamper switch.
506.5
Contents. The approved key box shall contain keys to gain necessary
access as required by the Fire Marshal.
506.6
Alarms. The key box may be connected to the building’s
fire alarm system. The tamper switch shall be as a trouble or supervisory
signal on the fire alarm system.
14. Delete
the provisions of Sections 508.5 and 508.5.1, including the exceptions
to 508.5.1 but retaining the provisions of Sections 508.5.2 through 508.5.6,
and substitute the following therefor:
508.5
Fire Hydrant Systems. This section defines water supplies for
fire department use for new buildings and structures. Fire hydrant systems
shall comply with Sections 508.5.1 through 508.5.6.
508.5.1
Water supply; where required. All buildings or structures shall
be served by a public water supply system meeting the following criteria:
The system shall be under pressure with an average static pressure of
not less than 35 pounds per square inch (psi). Flows shall be calculated
at 20 psi residual pressure. Water supplies shall be available for a
continuous four-hour duration. Water supplies shall be delivered under
pressure to fire hydrants located as follows:
508.5.1.1
Fire hydrants shall be located along public streets so that
no portion of the building will be over 300 feet from a fire hydrant.
Where this is not possible, additional hydrants shall be located on
the premises accessible to motorized fire apparatus.
508.5.1.2
One hydrant shall be located at each intersection and intermediate
hydrants shall be placed where the distance between intersections
exceeds 400 feet.
508.5.1.3
At least two (2) fire hydrants shall be located within 300 feet of
the building.
508.5.1.4
Additional fire hydrants shall be provided within 500 feet of the
building so that the fire flow required divided by 1,000 will equal
the number of hydrants available.
508.5.1.5
Hydrants shall be located approximately ten (10) feet from an all-weather
roadway. If this cannot be done, the closest part of the hydrant shall
be set back at least five (5) feet from the curb line.
508.5.1.6
A fire hydrant shall be located within 75 feet of the fire department
connection.
508.5.1.7
Hydrants shall be located approximately 50 feet from the building
to be protected.
508.5.1.8
Access to fire hydrants shall be all-weather roadways adequate in
width, clearance and strength for fire fighting purposes. Such routes,
including private roadways, shall be maintained accessible during
all seasons of the year. Legal provisions will be required for private
roads.
508.5.1.9
Fire hydrants shall meet the requirements of the City of St. Charles
and the standards of the American Water Works Association, and shall
have two and one-half (2½) inch outlets and one (1) four and
one-half (4½) inch outlet with auxiliary gate valves on the
hydrant branch line. Threads shall be American National Standard.
Pumper outlets shall face roadways.
15. Amend
Section 605.1 to read as follows:
605.1
Abatement of Electrical Hazards. Identified electrical hazards
shall be abated. Identified hazardous electrical conditions in permanent
wiring shall be brought to the attention of the code official responsible
for enforcement of the electrical code as adopted in Section 15.04.040
of the St. Charles Municipal Code. Electrical wiring, devices, appliances
and other equipment that is modified or damaged and constitutes an electrical
shock or fire hazard shall not be used.
16. Add
Section 605.10 as follows:
605.10
Ground fault protection. Ground fault protection of equipment,
including a remote key operated shunt trip switch, shall be provided
for any service of 800 amperes and above.
17. Add
Section 610.2.1 as follows:
610.2.1
Protection of kitchen exhaust ducts. All commercial kitchen
exhaust ducts shall be protected by a U.L. listed one- (1-) hour fire-rated
assembly. A listed kitchen duct wrap is an approved method.
18. Amend
Section 901.6 to read as follows:
901.6
Inspection, testing and maintenance. Fire detection and alarm
systems, fire extinguishing systems, fire hydrant systems, fire standpipe
systems, fire pump systems, private fire service mains and all other
fire protection systems and appurtenances thereto shall be subject to
acceptance tests as contained in the installation standards and as approved
by the fire code official. The fire code official shall be notified
before any required acceptance testing. A qualified technician shall
annually inspect, test and maintain all fire protection systems, including
but not limited to fire alarm, sprinkler systems and fire pumps.
19. Amend
Section 901.7 and add Section 901.7.1 as follows:
901.7
System out of service. Where a required fire protection system
is out of service, the fire department and the fire code official shall
be notified immediately and, where required by the fire code official,
the building shall either be evacuated or an approved fire watch shall
be provided for all occupants left unprotected by the shut down until
the fire protection system has been returned to service. Automatic fire
suppression systems shall not be out of service for more than eight
(8) hours for maintenance or repairs. A fire watch by a competent person
is required until repairs are completed.
901.7.1
Vacant buildings. Vacant buildings or unoccupied buildings
or portions of shall maintain all required sprinkler and standpipe
systems and all component parts in a workable condition at all times.
Fire alarm systems shall be maintained in operating condition at all
times. The system shall be tested in the presence of the Code Official
upon restoration to use.
20. Delete
the provisions in Section 903.2 “Automatic Sprinkler Systems –
Where Required” inclusive of subsections 903.2.1 through 903.2.13
and Table 903.2.13 and substitute the following therefore:
903.2 Where required. An automatic fire suppression system shall be installed and maintained in full operating condition throughout every story and basement of all buildings subject to this code.
Exception: Unoccupied structures of less than 400 square feet, considered low hazard and located not less than 100 feet from another structure. The requirements shall be subject to modifications by the authority having jurisdiction to compensate for particular building conditions to meet the intention of the code. (Ord. 2008-M-4 § 1.)
21. Delete
the provisions of Section 903.3.1.2 “NFPA 13R Sprinkler Systems”
(pg. 168) in its entirety and substitute the following therefore:
903.3.1.2
NFPA 13R Sprinkler Systems. NFPA 13R Sprinkler systems are
allowed only in one- and two-family dwellings; if provided, they shall
be installed throughout in accordance with NFPA 13R.
22. Delete
the provisions of section 903.3.5.1.1 “Limited Area Sprinkler System”
(pg. 169) and substitute the following therefore:
903.3.5.1.1
Limited Area Sprinkler Systems. Limited area sprinkler systems
serving fewer than five (5) sprinklers on any single connection are
permitted to be connected to the domestic service where a wet automatic
standpipe is not available. Limited area sprinkler systems connected
to domestic water supplies shall comply with each of the following requirements:
23. Delete
Exceptions No. 3 and No. 5 of Section 903.4 “Sprinkler System Monitoring
and Alarms” (pg. 169) in their entirety.
24. Add
Section 903.7 as follows:
903.7
Sprinkler system tests:
- The
main drain valve(s) and all other control valves on all sprinkler systems
shall be operated at least two (2) times per year to determine that
there is a free water flow at adequate pressure and that all other valves
operate freely and that supervisory service, if any exists, is operating
properly.
-
An internal inspection of the piping shall be performed periodically,
but at least once every ten (10) years to check for debris buildup,
and the piping is to be flushed if needed. If debris is noted, internal
inspections shall be at five (5) year intervals thereafter.
-
Each dry pipe valve shall be cleaned and reset at least once each year.
-
Automatic antifreeze solution systems and limited area systems that
are supplied from a domestic water source and which are not required
to provide a test line shall be exempt from the requirements of this
section.
-
All inspector’s test valve(s) shall be operated on a monthly basis
to assure the proper operation of the sprinkler system. An inspector’s
test valve is required at the end of each sprinkler system.
-
Where automatic sprinklers provide protection to an area, approved flow
and tamper switches interconnected to the fire alarm system shall be
provided. Each floor and each area over 15,000 square feet in area shall
be separately zoned. Each type of system (sprinkler, halon, kitchen,
HVAC, etc.) shall be zoned separately. Each sprinkler system need only
be zoned per floor.
-
All fire alarm and fire suppression systems shall have an outside alerting
device of a type and at a location approved by the Fire Marshal. Additional
smoke detection is not required in buildings with an automatic sprinkler
system unless required by a specific use group.
25. Delete
the provisions of Section 907.2 “Where required” and substitute
the following therefore:
907.2
Where required. An approved manual, automatic or manual and
automatic fire alarm system shall be provided in new buildings and structures
in accordance with Sections 907.2.1 through 907.2.23. Where automatic
sprinkler protection, installed in accordance with Section 903.3.1.1
or 903.3.1.2, is provided and connected to the building fire alarm system,
automatic heat detection required by this section shall not be required.
An approved automatic fire detection system shall be installed in accordance
with the provisions of this code and NFPA 72. Devices, combinations
of devices, appliances and equipment shall comply with Section 907.1.2.
The automatic fire detectors shall be smoke detectors, except that an
approved alternative type of detector shall be installed in spaces such
as boiler rooms where, during normal operation, products of combustion
are present in sufficient quantity to actuate a smoke detector. Notwithstanding
any provision of Section 907 and its subsections to the contrary, an
approved manual fire alarm signaling system shall be installed and maintained
in all buildings over one (1) story in height or over 1,000 square feet.
26. Delete
all of the Exceptions to 907.2.3 “Group E,” in their entirety.
27. Delete
the provisions of Section 907.3 “Where required – retroactive
in existing buildings and structures” and substitute the following
therefore:
907.3
Where required – retroactive in existing buildings and structures.
An approved manual, automatic or manual and automatic fire alarm system
shall be installed in existing buildings and structures in accordance
with Sections 907.3.1 through 907.3.1.8. Where automatic sprinkler protection,
installed in accordance with Section 903.3.1.1 or 903.3.1.2, is provided
and connected to the building fire alarm system, automatic heat detection
required by this section shall not be required.
An approved
automatic fire detection system shall be installed in accordance with
the provisions of this code and NFPA 72. Devices, combinations of devices,
appliances and equipment shall be approved. The automatic fire detectors
shall be smoke detectors, except that an approved alternative type of
detector shall be installed in spaces such as boiler rooms where, during
normal operation, products of combustion are present in sufficient quantity
to actuate a smoke detector. Notwithstanding any provision of Section
907 and its subsections to the contrary, an approved manual fire alarm
signaling system shall be installed and maintined in all buildings over
one (1) story in height or over 1,000 square feet.
28. Delete
Exceptions 1 and 2 to 907.3.1.1 “Group E” in their entirety.
29. Add
a Section 907.3.1.9 “R-1 and R-2 in buildings with multiple uses”
as follows:
907.3.1.9
R-1 and R-2 in buildings with multiple uses. Where a building
contains uses in groups R-1 and/or R-2 (where used as hotels, motels,
lodging houses, dormitories, apartments and similar occupancies) and
one or more additional uses classified in other use groups, the building
shall be equipped with an approved fire alarm system.
30. Delete
the Exception of Section 907.4.1 “Location” in its entirety.
31. Delete
the provisions of Section 907.15 “Monitoring” and its exceptions
and substitute the following therefore:
907.15
Supervisory service. Where required by this chapter or the
International Fire Code, an approved supervising station in accordance
with NFPA 72 shall monitor fire alarm systems. All required fire protective
signaling systems shall transmit alarm and trouble signs to an approved
central station, proprietary system, or remote-station system, and shall
be approved by the Fire Department. The following methods are approved:
1. Direct
connect
2. AES Radio
3. Or other methods approved by the Fire Official
Exception:
Supervisory service is not required for:
1.
Single- and multiple-station smoke alarms required by Section 907.2.10.
2. Smoke detectors in Group I-3 Occupancies
32. Delete
the provisions of Section 907.20.2 and its exception, and substitute the
following therefore:
907.20.2
Testing. Testing of automatic fire alarm systems and all alarms
which monitor control valves and flow switches for fire protection and
fire alarm equipment shall be performed monthly or more frequently where
required by NFPA 72 or by the Fire Code Official. Where automatic testing
is performed at least weekly by a remotely monitored fire alarm control
unit specifically listed for the application, the manual testing frequency
shall be permitted to be extended to annual.
Exception:
Devices or equipment that are inaccessible for safety considerations
shall be tested during scheduled shutdowns where approved by the Fire
Code Official, but not less than every 18 months.
33. Add
a Section 907.20.2.1, as follows:
907.20.2.1
Records. The written record of all tests shall contain the
following information:
- The
date and time of all tests.
- The
name or initials of the person who conducted the test.
- The
water pressure on the sprinkler riser gauge before and after each
test (sprinkler only).
- Any
problems found before, during, or after each test.
- Provide
a diagram showing areas served by control valves shall be placed adjacent
to each valve.
34. Add
a Section 907.21 “Alarms out of service” as follows:
907.21
Alarms out of service. No alarm shall be out of service for
more than 24 consecutive hours without the approval of the Fire Marshal.
Continuous guard service as approved by the Fire Marshal is required
for any building where the alarm will be out of service for 24 hours
or more.
35. Amend
the provisions of Section 909.1 “Scope and purpose” (pg. 181)
by adding the following:
Section
909.1.1 Where required. An emergency smoke control system is
also required when one or more of the following applies:
- In
all sprinklered buildings with a gross (total of all floors) floor
area of 40,000 square feet or more.
- In
all nonsprinklered buildings with a gross floor area of 7,500 square
feet or more.
- In
all buildings over three (3) stories or thirty-five (35’) feet
in height.
- In
buildings with multi-storied atriums.
- In
covered malls including anchor stores and tenant spaces.
36. Amend
the provisions of Section 909.2 “General Design Requirements”
(pg. 181) by adding the following:
909.2.1
Design criteria. Mechanical or gravity venting may be utilized.
Mechanical venting shall provide not less than six (6) air changes per
hour, in addition to meeting the other criteria of this Section. Gravity
venting shall conform to nationally accepted practices based upon the
anticipated smoke production and cubic area to be vented. For ordinary
hazards, gravity roof venting shall not be less than a 1:100 factor,
and such vents shall be spaced not more than 120 feet on centers.
37. Amend
Section 909.16 “Firefighter’s smoke control panel” (pg.
186) to read as follows:
909.16
Firefighter’s smoke control panel. A firefighter’s
smoke control panel for fire department emergency response purposes
only shall be provided and shall include manual control or override
of automatic control for mechanical smoke control systems. The panel
shall be located in a fire command center complying with Section 911,
and shall comply with Sections 909.16.1 through 909.16.3. The location
and design of controls for all smoke control systems shall be subject
to the approval of the Fire Chief.
38. Amend
the provisions of Section 912.1 “Installation” and substitute
the following therefore:
912.1
Installation. The type (Siamese, Storz) and size of the fire
department connection shall be in accordance with the NFPA standard
applicable to the system design and shall be subject to approval of
the Fire Department, based upon an analysis of the building’s
size and use group. Generally, a 5-inch size, Storz type connection
is required. A locking type connection cap is required, and available
through the City-approved supplier. An application is available at the
Fire Prevention Office.
39. Add
subparagraph 6 to Section 1006.3 “Illumination emergency power”
as follows:
6. In
all rooms and spaces over 2,000 square feet in area with an occupancy
load of 20 or more.
40. Amend
the provisions of Section 1008.1.8.3 “Locks and Latches” by
deleting Conditions No. 2, 2.1, 2.2, 2.3 and 3.
41. Amend
the provisions of Section 1008.1.8.5 “Unlatching” by deleting
item No. 3 of the Exception in its entirety.
42. Delete
the provisions of Section 1008.1.8.6 “Delayed Egress Locks”
in its entirety.
43. Amend
the provisions of Section 1008.1.8.7 “Stairway Door” by deleting
items No. 3 of the Exception in its entirety.
44. Amend
the provisions of Section 1012.3 “Opening Limitations” by
deleting the first paragraph and substituting the following therefore:
1012.2
Opening limitations. Open guards shall have balusters or ornamental
patterns such that a 4-inch diameter (102 mm) sphere cannot pass through
any opening up to a height of 34 inches (864 mm). From a height of 34
inches (864 mm) to 42 inches (1067 mm) above the adjacent walking surfaces,
a sphere 8 inches (203 mm) shall not pass. In occupancies in Groups
A, B, E, I-1, I-2, I-4, M and R and in public garages and open parking
structures, guards shall not have an ornamental pattern or design that
would provide a ladder effect.
45. Delete
the Exception to Section 1014.1 “Exit or Exit Access Doorways Required”
(pg. 210) and substitute the following therefore:
Exception:
Group I-2 occupancies shall comply with Section 1013.2.2. All Group
H, I and R-2 occupancies shall provide two exits or exit access doorways
from any space, regardless of occupant load or egress distance.
46. Delete
Table 1014.1 “Spaces With One Means of Egress” (pg. 210) and
substitute the following therefore:
Table
1014.1
Spaces with One Means of Egress
Occupancy |
Maximum
Occupant Load |
| A,
B, E, M, U |
20 |
| H-1,
H-2, H-3 H-4, H-5, I-1, I-3, I-4 |
NA |
| R-1,
R-3, R-4 |
10 |
| S
|
20 |
47. Amend
Table 1016.1 to read as follows:
Table
1016.1
Corridor Fire Resistance Rating
Occupancy
|
Occupant
Load Served by Corridor
|
Required
Fire-Resistance Rating (hours)
|
Without
Sprinkler System |
With
Sprinkler System (c) |
H-1,
H-2, H-3 |
All |
Not
Permitted |
1 |
H-4,
H-5 |
Greater
than 30 |
Not
Permitted |
1 |
A,
B, E, F, M, S, U |
Greater
than 30 |
1 |
1 |
R |
Greater
than 10 |
1 |
1 |
I-2
(a), I-4 |
All |
Not
Permitted |
1 |
I-1,
I-3 |
All |
Not
Permitted |
1
(b) |
(a)
For requirements for occupancies in Group I-2, see Section 407.3
(b) For a reduction in the fire-resistance rating of occupancies in
Group I-3, see Section 408.7.
(c) Buildings equipped throughout with an automatic sprinkler system
in accordance with Section 903.3.1.1 or 903.3.1.2 where allowed. |
48. Delete Section 1018.2 “Buildings With One Exit” (pg. 214)
and Table 1018.2 in its entirety and substitute the following therefor:
1018.2
Buildings with one exit. Only one exit shall be required in
buildings as described in Section 1014.1.
49. Amend
the provisions of Section 1023.3 to read as follows:
1023.3
Exit discharge location. Exterior balconies, stairways and
ramps shall be located at least 10 feet (3048 mm) from adjacent lot
lines and from other buildings on the same lot unless the adjacent building
exterior walls and openings are protected in accordance with Section
704 based on fire separation distance. Exit doors in exterior walls
shall be provided and spaced not more than 150 feet apart.
50. Amend
Section 2206.2.2 “Above-ground tanks located inside buildings”
to read as follows:
2206.2.2
Above-ground tanks located inside buildings. Above-ground tanks
for the storage of Class I, II and IIIA liquid fuels are not allowed
to be located in buildings.
51. Amend
Section 2206.2.3 “Above-ground tanks located outside, by deleting
the same in its entirety, including the four numbered subparagraphs thereto
and Table 2206.2.3, to read as follows:
2206.2.3
Above-ground tanks located outside, above grade. The storage
of flammable or combustible liquids in outside aboveground tanks is
prohibited within the corporate limits of the City of St. Charles, Illinois,
except by Special Permit issued by the Fire Chief. Compliance with the
following criteria is required for the issuance of a Special Permit
for such use:
- The
aboveground tank site is required to be a minimum of 100 feet to the
property line, except residential, educational, institutional, and
assembly occupancies which shall be 300 feet. The location of the
aboveground tank shall also comply with such additional and further
regulations as may be provided in the City of St. Charles’s
Zoning Ordinance and other requirements provided by law. The tank
location shall not be located in such a fashion that in the opinion
of the Fire Chief constitutes a threat to life or property.
- Buildings
on the same parcel shall be at least 50 feet from the tank site.
- A
site plan for the installation of the aboveground tank shall be submitted
to the Fire Official showing all buildings and structures on the same
parcel.
- Fixed
fire protection systems shall be provided for all aboveground tank
installations over 500 gallons in capacity.
- At
least 2 (two) fire hydrants shall be provided within 300 feet of the
aboveground tank.
- The
minimum flow for each hydrant shall be 1,000 gallons each.
-
The fire flow duration shall be 60 minutes for flows up to 1,000
gpm; 2 hours to 2,000 gpm, and 3 hours for 3,000 gpm.
- An
evacuation plan shall be developed and submitted to the Fire Official
for review and approval for all properties within ¼ mile of
the aboveground tank.
- A
description of the proposed truck routes used to serve the tank (fill/discharge)
shall be provided to the Fire Official for review and approval.
- A
site plan and complete description shall be provided to the Office
of the Illinois State Fire Marshal for review and approval.
- All
aboveground storage tanks shall be 2 (two) hour fire-rated and U.L.
listed (ULI 2085).
- The
maximum number of tanks at one business location is one (1) tank.
- The
maximum size shall not exceed 1,000 gallons capacity.
- The
aboveground tank shall be provided with tank containment or diking
to equal the maximum tank capacity plus the fire flow noted above.
- The
aboveground tank shall be protected with physical barriers per Section
312.2.
- Aboveground
storage tank(s) shall not be for use by the general public nor shall
any liquid contained in an aboveground tank be transferred into any
type vessel or device to be used or controlled by the general public.
- All
aboveground tank installations shall be enclosed by a metal cyclone
type fence with screening attached. A metal roof structure shall be
provided to provide protection from the weather, and include the secondary
containment area or dike. Each tank shall be provided with a minimum
of 3 (three) feet of clear space for maintenance and inspection.
- No
liquid shall be stored in an aboveground tank that has a flash point
less than that of gasoline or -36 to -45 degrees F.
- An
automatic shutoff device capable of stopping the delivery of fuel
into a storage tank at 90% of the tank capacity shall be provided.
- Tank
contents must be transferred by means of fixed pumps only. Pumps must
be designed and equipped so as to prevent accidental discharge.
- All
tank openings associated with piping, vents, and inspections, shall
be through the top of the tank only.
- Approved
anti-siphon devices shall be installed at each connection of the piping
to the tank when such piping extends below the level of the top of
the tank.
- U.L.
listed, portable ABC type fire extinguisher(s) shall be provided.
- No
parking is allowed within 50 feet of an aboveground tank.
- All
aboveground tank plans must include the following:
- Site
plans as mentioned above.
-
Aboveground tank details including all piping systems, pump and
transfer systems, manufacturer’s tank specifications, and
all site protection, safety equipment, and safety signage per
NFPA 704.
-
The aboveground tank requires a City of St. Charles Building Permit,
and 4 (four) sets of plans and specifications are required.
-
Approval for all aboveground tank installations shall be by the
Fire Chief (or his designee) and the Building Official.
52. Amend
Section 2401.1 “Scope” to read as follows:
2401.1
Scope. Tents, canopies and membrane structures shall comply
with this chapter. Air-supported structures and membrane structures
that are air-supported or air-inflated are prohibited. References in
the 2003 International Fire Code to air-supported or air-inflated structures
as being permitted shall be disregarded.
53. Amend
Section 2703.1 “Scope” to read as follows:
2703.1
Scope. The storage, use and handling of all hazardous materials
shall be in accordance with this Section. Hazardous materials are not
permitted uses except by specific approval of the Fire Chief on a case-by-case
basis. Such approval shall be based on an analysis of the products,
processes and applications involved and on the criteria listed in this
Section, Exhibit A.
54. Delete
the provisions of Section 2703.2.4.2 “Aboveground tanks” in
its entirety, including the exception and section 2703.2.4.2.1. (See Section
2206.2.3 for applicable regulations.)
55. Add
Section 3301.2 “Permit required” to read as follows:
3301.2
Permit required. Permits shall be required as set forth in
Section 105.6 and regulated in accordance with this section. An application
for permit, on a form developed by the Fire Official, shall be made
in writing at least thirty (30) days in advance of the display of fireworks
or discharge of explosives.
56. Amend
3301.2.4.2 to read as follows:
3301.2.4.2
Fireworks display. The permit holder shall furnish a bond or
certificate of insurance in an amount deemed adequate by the Fire Chief
for the payment of all potential damages to a person or persons and
to property by reason of the permitted display, and arising from any
acts of the permit holder, the agent, employees or subcontractors. The
minimum amounts that may be required by the Fire Chief are Public Liability
Insurance in the amount of not less than $1,000,000 bodily injury and
$250,000 property damage, with the City of St. Charles named as an additional
insured.
57. Amend
Section 3405.1 “Scope” to read as follows:
3405.1
Scope. Dispensing, use, mixing and handling of flammable liquids
shall be in accordance with Section 3403 and this Section. Tank vehicle
and tank car loading and unloading and other special operations shall
be in accordance with Section 3406. Flammable or combustible liquids
shall not be dispensed by gravity from tanks, drums, barrels or similar
containers. Approved pumps that take suction from the top of the container
shall be used. Special type dispensers, such as coin, key or card operated
devices, for self service operation by the general public are prohibited.
No tank vehicle shall be left unattended on any lot, street, highway,
avenue, alley, or any other location, public or private.
Exception:
1. When necessary due to the viscosity of the liquid, the Fire Chief
may permit special methods.
2. Containers of organic coatings having no fire point and which are
opened for pigmentation are not required to comply with this Section.
58. Delete
Section 3404.2.8 “Vaults” in its entirety, including Sections
3404.2.8.1 through 3404.2.8.18.
59. Delete
Section 3404.2.9 “Above-ground tanks” in its entirety, including
Sections 3404.2.9.1 through 3404.2.9.6.10. (See section 2206.2.3 for applicable
requirements.)
60. Amend
Section 3404.2.12 to read as follows:
3404.2.12
Testing of underground tanks. Before being covered or placed
in use, tanks and piping connected to underground tanks shall be tested
for tightness in the presence of the Fire Code Official. Piping shall
be tested in accordance with Section 3403.6.3. The system shall not
be covered until it has been approved. All tanks and piping shall be
retested every five years when less than 15 years of age and every two
years thereafter.
61. Add
a Section 3701.3 “Notice” to read as follows:
3701.3
Notice. The owner of any business required under the provisions
of the ILLINOIS TOXIC SUBSTANCES ACT to post notice to the employees
of such business in relation to the presence of toxic substances shall
display such notice in accordance with the provisions of such ACT.
62. Add
a Section 3701.4 “Emergency Contingency Plan” to read as follows:
3701.4
Emergency Contingency Plan. The owner shall notify all employees
of the Emergency Contingency Plan required under the ILLINOIS TOXIC
SUBSTANCES ACT. The plan shall be posted along with the notice in relation
to toxic substances noted in 3701.3.
63. Add
section 3801.4. “Storage Prohibited/Permit Required” to read
as follows:
3801.4
Storage Prohibited/Permit Required. Aboveground storage of
liquefied petroleum gas utilizing one or more containers having a total
capacity of over 1,000 gallons water capacity shall be prohibited. Any
tank installation using containers over 30 gallons or aggregate capacity
over 60 gallons water capacity shall require a Permit issued by the
Fire Official. All portable propane cylinders (regardless of size) shall
be stored in approved racks outside the building.
64. Add
section 3801.5 to read as follows:
3801.5
Parking Restrictions. No tank vehicle shall be left unattended
on any lot, street, highway, avenue, alley or any other location, public
or private.
65. Add Exhibit A:
Exhibit
A
Performance
Guidelines for High Hazard Uses in the City of St. Charles
- Specific
location: The geographic location and distances to other structures,
rivers, streams, and other use groups.
- Zoning:
The proximate distances to assembly, educational, institutional, and
residential uses and vacant land zoned for these uses.
- Types
of hazardous materials which are not allowed: Materials listed in Section
307.3 High Hazard Group H-1 that present a detonation hazard shall not
be permitted under any circumstances.
- Allowable
construction types: Type I and II only.
- Required
fire protection for High Hazard materials:
a. Provide extra hazard Group II fire sprinkler system
b. Provide a fixed foam fire protection system
- Required
water supply system: 3,000 to 6,000 gallons per minute from a reliable
source.
- Required
review of the maximum allowable quantities per the control areas and
compliance with Sections 414, 415, 416, 417 and 418.
- Required
review for potential for:
a. Noise
b. Glare and heat
c. Vibration
d. Dust or air pollution
e. Odor
f. Electromagnetic interference
g. Water pollution and containment
h. Hazardous waste and by-products
- Required
safeguards provided for toxic substances.
- Review
of hazardous materials truck routes to and from the site.
- Elevation
of product handling and transfer.
- Separation
between high hazard areas and other use areas within the same building
shall be provided by means of a four (4) hour rated reinforced solid
masonry wall.
- Submittal
and review of all hazardous materials MSDS.
- A specific
evacuation plan is required for the building and surrounding area.
- A contingency
plan is required for any spill or release of product to mitigate the
hazard and provide a complete listing of persons to contact.”
(Ord. 2004-M-76
§ 1; Ord. 1988-M-15 § 1; Ord. 1978-M-37 Art. 5 (part).)
15.28.060 Water supplies for Fire Department use.
A. This
section applies to newly constructed buildings and structures and to those
buildings or structures increased in height or area.
B. All buildings
or structures shall be served by a public water supply system meeting
the following criteria. This system shall be under pressure with an average
static pressure of not less than 35 pounds per square inch (psi). Flows
shall be calculated at 20 psi residual pressure. The supplies shall be
available for a continuous four-hour duration except that flows less than
2,000 gpm shall be available for a two-hour duration.
C. Consistent
with proper fire prevention, the following water supplies shall be available
commensurate with hazards therein:
Type
of Development or use |
Flow
required in Gallons per Minute |
| A.
Single-family Detached Residential |
1,000
to 1,500 |
| B.
Two-family and Townhouse Residential |
1,500
to 2,000 |
| C.
Multi-family |
3,000
to 4,000 |
| D.
Industrial and Storage |
3,000
to 5,000 |
| E.
Research & Development Labs |
3,000
to 4,000 |
| F.
Business and Commercial Areas |
3,000
to 4,500 |
| G.
Mercantile Centers |
3,000
to 6,000 |
| H.
Assembly and Educational |
3,000
to 5,000 |
| I.
Health Care and Institutional |
3,000
to 4,000 |
(Ord. 2004-M-76
§ 1; Ord. 1988-M-15 § 1; Ord. 1978-M-37 Art. 5 (B).)
15.28.070
Emergency Conditions.
In case
there shall be, in the opinion of the Fire Official, actual and immediate
danger to life and property from the hazards of fire and explosion arising
from the storage, handling, or use of hazardous substances, materials,
or devices, or from conditions hazardous to life and property in the use
or occupancy of buildings or premises, the Fire Official shall employ
such labor and machinery, equipment and devices and cause the necessary
work to be done to render said occupants or property temporarily safe,
whether the procedure prescribed in this section has been instituted or
not.
- Where
practical and time constraints permit, the owner, occupant or other
person responsible for the emergency condition shall be notified of
the emergency condition, in writing, and shall have the option of making
the condition safe.
-
The owner and occupants of the premises shall be jointly and severally
liable for any costs incurred in connection with the same.
-
The Fire Official of the City of St. Charles, Illinois, shall cause
proper action to be instituted against the owner of the premises, and
the occupants if different than the owners, for the recovery of costs
incurred by the City of St. Charles, Illinois, in the performance of
the emergency work.
- For the purposes of this Article, the following words and phrases shall have the meanings respectively ascribed to them:
a. “Hazardous Substance” or “Hazardous Material” means any substance or material or mixture of substances which is toxic, corrosive, an irritant, strong sensitizer, radioactive, flammable, combustible, or which generates pressure through decomposition, heat or other means and which may cause injury, or illness to humans, domestic livestock, or wildlife or as defined by the Illinois Environmental Protection Act or any federal law.
b. “Hazardous material Incident” means an incident which threatens public health or safety involving the actual or potential release of a hazardous substance or hazardous material.
c. “Toxic” means any substance (other than a radioactive substance) which has the capacity to produce bodily injury or illness to man through ingestion, inhalation, or absorption through any body surface.
d. “Corrosive” means any substance which, in contact with living tissue, causes destruction of tissue by chemical action, but does not refer to action or inanimate surfaces.
e. “Irritant” means any substance, no corrosive, which, on immediate, prolonged or repeated contact with normal living tissue, will induce local inflammatory reaction.
f. “Strong Sensitizer” means any substance with will cause on normal living tissue through an allergic or photo dynamic process, a hypersensitivity of the same substance.
g. “Radioactive” means any substance which emits ionizing radiation.
h. “Flammable” means any substance which has a flash point of less than 100 degrees Fahrenheit.
i. “Combustible” means substance with a flash point greater than 100 degrees Fahrenheit.
j. “Person” shall mean any individual, partnership, corporation, trust, firm, company, estate, association, or other legal entity.
Control of Hazardous Substances or Hazardous Materials:
a. It shall be unlawful for any person to use, store, deliver or transport hazardous substances or hazardous materials, or cause the use, storage, delivery of transporting of hazardous substances or hazardous materials in any manner inconsistent wit the requirements of the Fire Prevention Code of the City of St. Charles or any other applicable City ordinance, County ordinance, State law or Federal law.
b. It shall be unlawful for any motor vehicle carrying, transporting or containing a hazardous substance or hazardous material to park or stand, other than temporarily for the purpose of, and while actually engaging in, loading or unloading, on private property, without the knowledge and express consent of the person who is in charge of the property and who is aware of the nature of the hazardous substance or hazardous material the motor vehicle contains.
c. It shall be unlawful for any person using, storing, manufacturing, producing, disposing, treating, transporting or causing the use, storage, manufacture, production, disposal, treatment or transportation of any hazardous substance or hazardous material in any manner which results in a hazardous materials incident.
Hazardous Materials or Hazardous Substance Incident Expense Recovery:
a. Any person causing or permitting a hazardous material incident shall be responsible for all of the following:
1) Reimbursement in full, of any and all costs incurred by the CITY in connection with the operation (including equipment and vehicles), maintenance, and staffing required to respond to such hazardous materials incident. Vehicles and staffing will be charged the hourly rate of pay, including overtime expenses and overhead costs, for each employee who participates in such response to a hazardous materials incident. Any maintenance costs incurred by the CITY will be reimbursed at the rate of time and materials.
2) Reimbursement, in full, for any and all costs incurred by the CITY for equipment and material s used, damage, lost, spent, destroyed or rendered irreparable in connection with a hazardous materials incident.
3) Assumption of, and all liability and costs for, any cleanup or removal resulting from any hazardous material incident, including but not limited to any independent cleanup contractor necessitated by such hazardous material incident.
4) Any and all costs and reasonable attorney's fees incurred in connection with the enforcement of the Ordinance and any collection undertaken hereunder.
b. The City of St. Charles shall prepare and forward to the person or persons causing or permitting a hazardous material incident a bill for the total costs and expenses incurred for which such person or persons are responsible pursuant to this Section; provided, however, any costs in connection with any independent cleanup contractor shall be billed directly by such contractor. Payment of the total bill shall be made within thirty (30) days of receipt. Any bill or portion of a bill remaining unpaid after thirty (30) days of receipt shall accrue interest on the unpaid balance at the rate of 1 ½% per month, or fraction of month.
Limitation of Liability: The City, its officers, agents or employees, shall not have any liability or responsibility for any claim, injury, or damage of any kind resulting from a hazardous material incident to which the City or any of its departments, officers, agents or employees responds.
Invalidity: Should any clause, sentence, paragraph or part of this Ordinance be declared a court of competent jurisdiction to be invalid, such decision shall not affect the validity of the Ordinance as a whole or any part thereof, other than the part so declared to be invalid.
(Ord. 2006-M-59; Ord.2006-M-25 Pgrph D; 2004-M-76 § 1; Ord. 1988-M-15 § 1; Ord. 1978-M-37 Art. 5 (B).)
(Ord. 2004-M-76
§ 1; Ord. 1988-M-15 § 1; Ord. 1978-M-37 Art. 5 (B).)
15.28.080
Fire Department Access.
A. Public
or private access shall be provided to each building so that the first
responding fire department pumper unit will be so located that all points
of the interior of the building may be reached by 150 feet of fire department
initial attack hose.
Exception
- Where size of building and height of building do not allow this criteria
to be met and interior standpipe system connected to a public water system
and equipped with a fire department connection, the above criteria may
be considered met when approved by the Fire Prevention Bureau.
B. Public
or private access for motor fire apparatus shall be provided around the
building so that it may be properly laddered and operation of mechanical
elevated mechanism may be properly utilized. Minimum width of the access
routes shall be 20 feet with greater widths to accommodate vehicles when
turning.
C. Access
routes shall be so arranged that fire department apparatus may respond
from all points of the building to adjacent fire hydrants along routes
not to exceed 300 feet from the most remote point of the building to the
closest fire hydrant.
D. Fire
lanes on private property shall be approved by the Bureau of Fire Prevention
and parking of motor vehicles or otherwise obstruction such fire lanes
or access routes shall be prohibited at all times.
E. Private
fire department access roads and ways shall be properly designed, maintained
and accessible at all times.
F. Access
routes shall be circulating for adequate fire apparatus movement.
G. Access
roads shall be not less than 15 feet from buildings.
(Ord. 2004-M-76
§ 1; Ord. 1978-M-37 Art. 5 (C).)
15.28.090 Deferral of Certain Improvements.
A.
In General. Certain upgrades and improvements to buildings required
under this Chapter which are designed for the protection of the owner's
property, but not for the protection of life or the property of others,
may be deferred for a specified amount of time, in accordance with the
standards stated in this Section.
B. Application.
An Application for the Deferral of Upgrades or Improvements under this
Section may be made by the owner of any building or structure to the Chief
of the Fire Department, (e.g., "the Fire Chief"), on a form
provided by the Fire Department, containing all information required on
such form, along with the following information:
- The legal
description of the property for which deferral is requested;
- Proof
of the current ownership of the real estate parcel, and the names and
addresses of all occupants of the building or structure;
- If the
real estate parcel is owned by a land trust, a verified identification
of all beneficiaries, in compliance with the Illinois Land Trust Beneficial
Interest Disclosure Act (765 ILCS 405);
- The
specific upgrades or improvements for which deferral is requested;
- The
reasons which the applicant relies upon as justifying the requested
deferral, specifically referring to the standards for deferral set forth
below;
- A current
Plat of Survey of the parcel, showing all lot lines, all existing and
proposed buildings and structures located on the parcel, all adjoining
streets, and the distances between the buildings or structures on the
parcel to buildings or structures on adjoining parcels;
- Any
other evidence, documents or other materials available to support the
Application, and to establish that the standards for deferral set forth
below have been met, including any additional information requested
by the Fire Chief or his designee.
The application shall be signed and verified by the current owner, and
all current occupants, of the real estate parcel for which deferral
is sought.
C. Standards
for Deferral of Upgrades or Improvements. The Fire Chief may
permit the deferral of specific improvements or upgrades required under
this Section only if the evidence submitted by the applicant establishes
each of the following conditions:
- The deferral
of the upgrades or improvements will not increase the risk to the safety
of any persons on the premises, or to the property of others; and
- Deferral
of the specific improvements or upgrades is necessary to alleviate a
particular hardship upon the owner, as distinguished from a mere inconvenience
if the deferral is not permitted; and
- The
particular hardship is expected to be alleviated at some specific time
in the future; and
- The
particular hardship was not created by any current owner or occupant
of the property; and
- The
hardship to the owner would outweigh the benefits that would be obtained
by immediate completion of the upgrades or improvements.
D. Inspection
of Site. Upon receipt of the Application and all supporting documents,
the applicant shall arrange for an inspection of the site, and surrounding
properties, by the Fire Chief.
E.
Decision of Bureau. The Fire Chief shall either issue its permit
granting the requested deferral (either in whole or in part, and subject
to necessary conditions and restrictions), or deny the requested deferral.
Permits granting deferrals may contain such conditions and restrictions
as may be necessary to ensure compliance with the standards set forth
in this title and section, and to implement the general purpose and intent
of this title. The Permit for Deferral shall be valid only if the owner
and all occupants of the parcel execute a Deferral Agreement (described
in Subsection F below). The Permit for Deferral shall expire within a
reasonable time after the particular hardship necessitating the deferral
is expected to be alleviated; provided, however, that no Permit for Deferral
shall be granted for more than five years.
F. Deferral
Agreement. Every Permit for Deferral shall be contingent upon
the record owner, and all occupants of the parcel, signing a Deferral
Agreement which shall legally describe the property subject to the Permit
for Deferral, and shall specifically set forth all sections of this title
which are being deferred, and the expiration of the deferral period; and
shall contain the agreement of the record owner of the premises to complete
the required improvements and
upgrades prior to the expiration of the deferral period. The Deferral
Agreement shall then be recorded with the Kane County Recorder of Deeds.
(Ord. 2004-M-76
§ 1; Ord. 1978-M-37 Art. 5 (D).)
15.28.100
App |